DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-101ANN-BD (Announcement Circuit Pack)
9
Notes:
a. Error Type 1
This error indicates the circuit pack totally stopped
functioning or it was physically removed from the system.
NOTE:
The alarm is logged about 11-minutes after the circuit pack has
been removed or when the SAKI Test (#53) fails.
If the circuit pack is not in the system, insert a circuit pack (in the same
slot as the error indicates) to resolve this error. If the circuit pack is in the
system and the red LED is on, refer to ‘‘LED Alarms without Alarm Log
Entry or with Error Type 1’’
in Chapter 7, ‘‘LED Interpretation’’.
b. Error Type 14
This error is logged whenever the Announcement
Checksum Test (#209) fails. The Aux Data indicates the identifying number
of the first defective announcement found. This number corresponds to
the announcement numbers on the announcement administration form.
The extension associated with the announcement can be determined with
the display announcement command. This error always appears in
conjunction with Error Type 2817. Follow the procedures for Error Type
2817 to troubleshoot Error Type 14.
c. Error Type 23
The circuit pack has been logically administered but not
physically installed. The alarm clears when the circuit pack is installed.
17676 In-line Error
2817(j) Announcement
Checksum Test
(#209)
MINOR ON test board UUCSS sh r 3
17682 In-line Error
17699(j) In-line Error
3840(l) Any None
3999 (o) Any None
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
Table 9-38. Announcement Circuit Pack Error Log Entries — Continued
Error
Type
Aux
Data Associated Test Alarm Level
On/Off
Board Test to Clear Value
Continued on next page