DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-83ANL-LINE, ANL-NE-L (8-Port Analog Line)
9
Battery Feed Test (also called Port Diagnostic
Test) (#35)
The battery feed chip provides power to the telephone equipment, signaling,
rotary dial pulsing, transmission, and balance. This test checks the signaling and
switchhook capabilities of the battery feed chip by terminating the port, applying
battery, and trying to detect a current.
Table 9-34. TEST #35 Battery Feed Test Results
Error
Code
Te s t
Result Description/ Recommendation
ABORT Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals for a maximum of 5 times.
1000 ABORT System resources required to run this test are not available. The port may
be busy with a valid call. This result is also reported for the system’s
Music-on-Hold port when it is off-hook, which it usually is.
1. Enter display port UUCSSpp to determine the station’s extension.
Enter status station extension to determine the service state of the
port. If the port is in use, it will be unavailable for certain tests. Wait
until the port is idle before retesting.
2. When the port is idle, retry the command at 1-minute intervals up to 5
times.
1004 ABORT System resources required to run this test are not available. The port may
be busy with a valid call.
1. Use the display port UUCSSpp command to determine the station
extension. Use the status station command to determine the service
state of the port. If the service state indicates that the port is in use,
then the port is unavailable for certain tests. (Refer to Chapter 8,
‘‘Maintenance Commands’’, for a full description of all possible
states.) You must wait until the port is idle before retesting.
2. Retry the command at 1-minute intervals for a maximum of 5 times.
3. If the test continues to abort and the port is not in use, escalate the
problem.
1005 ABORT The test was aborted due to a configuration problem. This code results
under either of the following conditions:
1. This test may not be applicable, or it may be disruptive to terminal
equipment other than a voice terminal (for example, the modem pool
member or music on hold).
2. The circuit pack is one of the following:
— TN742 vintages 13,14 and 15
— TN769 vintages 3,4 and 5
Continued on next page