DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-836EXP-INTF (Expansion Interface Circuit Pack)
9
2000 ABORT Response to the test request was not received within the allowable time period.
2100 ABORT System resources required to run this test are not available.
1. Retry the command at 1-minute intervals a maximum of 3 times.
9999 ABORT EI circuit pack reset successfully. Could not perform initialization test results
query because link to EPN is not up.
1. Execute release board PCSS. Wait one minute. Issue the display error
command. If you see Error Type 2049 logged against this EI circuit pack,
then the EI Test has failed with an error code equal to the aux data of this
entry. Otherwise, the initialization tests have passed.
12000 ABORT EI circuit pack reset successfully. Response to the initialization test results
query was not received within the allowable time period.
12100 ABORT EI circuit pack reset successfully. System resources required to run
initialization test are not available.
1. Retry the command at 1-minute intervals a maximum of 3 times.
12026 ABORT EI circuit pack reset successfully. It responded with an unknown reply to the
query for the results of its initialization tests.
1. Retry the command at 1-minute intervals a maximum of 3 times.
2. If the test continues to abort, replace the circuit pack or transceiver.
1 FAIL The EI did not successfully reset.
1. If the EI circuit pack is in the EPN, the EPN Maintenance Board may be
holding the EI circuit pack reset. Attempt to rectify this condition by
executing the test maint P long command on the maintenance board in
the same EPN.
2. If Step #1 was not successful in releasing the EI circuit pack, temporarily
remove the EPN maintenance circuit pack.
3. Repeat the reset board PCSS command.
4. If reset continues to fail, replace circuit pack.
5. Insert EPN maintenance circuit pack if it was removed.
2 FAIL The EI circuit pack was successfully reset, but it did not begin running after the
reset.
1. If the EI circuit pack is in the EPN, temporarily remove the EPN
maintenance circuit pack.
2. Repeat the reset board PCSS command.
3. Re-insert the EPN maintenance circuit pack if it was removed.
Table 9-316. TEST #224 Expansion Interface Test — Continued
Error
Code
Tes t
Result Description/ Recommendation