Maintenance Object Repair Procedures
9-1309PNC-DUP (PNC Duplication)
9
different switch nodes. Investigate any alarms against SN-CONF, SNI-BD,
FIBER-LK. The last two digits of the error code indicate the fiber-link
number (01-27) of the fiber that reported the retired alarm.
List fiber-link
gives the location of the fiber.
p. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_EAL. Use
status
pnc
to look at the state of health indexes for the PNCs, and investigate any
associated alarms. Adding 1 to the last two digits of the error code gives
the PN number of the port network that reported the retired alarm. (20003
points to port network 4.)
List config port-network
gives the cabinet
number associated with a port network.
q. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_INL. Use
status
pnc
to look at the state of health indexes for the PNCs, and investigate any
associated alarms. Adding 1 to the last two digits of the error code gives
the PN number of the port network that reported the retired alarm. (20103
points to port network 4.)
List config port-network
gives the cabinet
number associated with a port network.
r. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_HW. Use
status
pnc
to look at the state of health indexes for the PNCs, and investigate any
associated alarms. Adding 1 to the last two digits of the error code gives
the PN number of the port network that reported the retired alarm. (20203
points to port network 4.)
List config port-network
gives the cabinet
number associated with a port network.
s. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_PER. Use
status
pnc
to look at the state of health indexes for the PNCs, and investigate any
associated alarms. Adding 1 to the last two digits of the error code gives
the PN number of the port network that reported the retired alarm. (20303
points to port network 4.)
List config port-network
gives the cabinet
number associated with a port network.
t. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_DS1. Use
status
pnc
to look at the state of health indexes for the PNCs, and investigate any
associated alarms. Adding 1 to the last two digits of the error code gives
the PN number of the port network that reported the retired alarm. (20403
points to port network 4.) List config port-network gives the cabinet
number associated with a port network.
u. A spontaneous PNC interchange took place in response to the retiring of
an alarm on the B-PNC associated with fault class FC_SNIL. Use status
pnc to look at the state of health indexes for the PNCs, and investigate any
associated alarms. The last two digits of the error code indicate the
fiber-link number (01-27) of the fiber that reported the retired alarm. List
fiber-link gives the location of the fiber.