DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-644DS1-FAC (DS1 Facility)
9
DS1 Converter Performance Measurements
Report
The DS1 Converter Performance Measurements provide link performance
measurements for the DS1 facilities.
When no facility alarms exist on the DS1 facility, events that indicate a
degradation in the performance of the DS1 facility are monitored and recorded.
These events will generate appropriate alarms when performance of the DS1
facility has degraded below acceptable levels. These measurements include
errored seconds, bursty seconds, severely errored seconds, and failed seconds.
There are two DS1 Converter Performance Measurements Sub-reports. The first
sub-report, DS1 Converter Performance Measurements Summary Report,
provides information on the worst 15 minute interval of data, the total for 24 hours
of data and the current 15 minute counter for each of the above mentioned
counters.
The second sub-report, DS1 Converter Performance Measurements Detailed
Report displays a detailed log for the last 96 15-minute intervals for each of the
above mentioned counters.
The DS1 Converter Performance Measurements Summary Report can be
accessed with
list measurements ds1-facility summary UUCSSf
[print/schedule]
. A more detailed version of the report is accessed with
list
measurements ds1-facility log UUCSSf [print/schedule]
.
The user can reset all hardware and software measurement counters for a given
facility with
clear measurements ds1-facility UUCSSf
. The
Counted Since
time
is also reset and the
Number of Valid Intervals
count is set to zero.
The reports are printed on the screen or, by using the
print
option, on a printer
attached to the terminal.
Clearing Firmware Errors
DS1 CONV error reports are generated by firmware autonomously, they are not
associated with system technician demanded tests. Therefore,
test board clear
command does not affect the error status known by the DS1 CONV firmware. To
clear all the on-board firmware-detected errors unconditionally, execute the clear
firmware-counters command.