DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-1732TDM-CLK (TDM Bus Clock)
9
TDM Bus Clock Parameter Update Test (#151)
This test updates the following internal parameters on the Tone-Clock circuit
pack:
Disable in-line duplication status messages.
Disable in-line subrate frame maintenance messages (TN768, TN780
only).
Set the PPM threshold at 60 PPM for TN768 and TN780. Set the PPM
threshold at 85 PPM for TN2182.
Enable PPM threshold switching
Set the number of slips to trigger
loss of signal
- currently 30 per 5
millisecond period
Enable the on-board synchronization switching algorithm (see above)
Enable holdover operation (TN2182 only).
This is not a test and will always pass without identifying or reporting any
Tone-Clock circuit pack errors
Table 9-649. TEST #151 TDM Bus Clock Parameter Update Test
Error
Code
Tes t
Result Description/ Recommendation
ABORT Internal system error
FAIL Internal system error
1. Retry the command at 1-minute intervals a maximum of 5 times.
PASS The Tone-Clock circuit pack parameters have been successfully updated.
Continued on next page