DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-1322POWER
9
Error Log Entries and Test to Clear Values
Note:
a. This error occurs is valid only for AC-powered multi-carrier cabinets with
battery backup. For DC-powered cabinets, you cannot clear the error and
it should be ignored.
Battery Holdover (Large Batteries)
The large batteries are mounted inside a separate battery cabinet and can
supply holdover times of 2 to 8 hours depending on the size of the battery. The
batteries are circuit breaker protected and are charged by the J58890CH-1. The
batteries also contain a thermal sensor that change the charging voltage
depending on the battery temperature.
Table 9-514. Battery & Battery Charger Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
0 Any Any Any test environment UU sh r 1
1 Any Battery & Battery Charger
Query Test (#5) (error
code 8)
MINOR ON test environment UU s r 1
257 Any Battery & Battery Charge
Query Test (#5) (error
code 4)
MINOR ON test environment UU s r 1
769 Any Battery & Battery Charger
Query Test (#5) (error
code 2)
MINOR ON test environment UU s r 1
3840(a) 1005 or
1028
Associated Battery &
Battery Charger Query
Test (#5)
test environment UU s r 1