Maintenance Object Repair Procedures
9-869FIBER-LK (Fiber Link)
9
140 FAIL The endpoint 1 SNI is physically connected to a DS1 CONV but is not
administered to be connected to a DS1 CONV (list fiber-link can be used to
display fiber link endpoints). Either add the DS1 converter complex to the fiber
that this SNI is associated with by:
1. Check for the fiber that this SNI is an endpoint of by checking list
fiber-link.
2. Remove fiber-link for the fiber that this SNI is an endpoint of.
3. Add the fiber back via add fiber-link and this time administer the DS1
converter complex also. Or, remove the DS1 CONV connection and
connect the SNI directly to its administered fiber endpoint by entering list
fiber-link and verifying that the fiber optic cable and metallic cable
connections are installed as administered.
202 FAIL The SNI circuit pack (endpoint 2) cannot communicate with the equipped SNI
in slot 2 (list fiber-link can be used to display fiber link endpoints).
1. Perform the ‘‘Fiber Fault Isolation Procedure’’
. This should resolve multiple
SNI-PEER errors.
2. If the SNI being tested has SNI-PEER Error Type 1, replace the SNI being
tested. Replacing an SNI may be service interrupting. Refer to the SNI-BD
section for the procedure for replacing an SNI. To view SNI-PEER errors,
use the display errors command with category PNC-PEER. Retry the
command.
3. If the SNI being tested still has SNI-PEER Error Type 1, replace the SNI in
slot 2.
203 FAIL The SNI circuit pack (endpoint 2) cannot communicate with the equipped SNI
in slot 3 (list fiber-link can be used to display fiber link endpoints).
1. Perform the ‘‘Fiber Fault Isolation Procedure’’
. This should resolve multiple
SNI-PEER errors.
2. If the SNI being tested has SNI-PEER Error Type 257, replace the SNI being
tested. Replacing an SNI may be service interrupting. Refer to the SNI-BD
section for the procedure for replacing an SNI. To view SNI-PEER errors,
use the display errors command with category PNC-PEER. Retry the
command.
3. If the SNI being tested still has SNI-PEER Error Type 257, replace the SNI in
slot 3.
Table 9-333. TEST #759 Configuration Audit — Continued
Error
Code
Tes t
Result Description/ Recommendation
Continued on next page