DEFINITY Enterprise Communications Server Release 7
Maintenance for R7r
555-230-126
Issue 4
June 1999
Maintenance Object Repair Procedures
9-1103M/T-ANL (Maintenance/Test Analog Port)
9
Analog Port Sanity Test (#963)
This test verifies that the port circuitry involved in the analog trunk testing on the
Maintenance/Test Analog Port is functioning properly.
This test will abort if an ATMS Test Call is in progress on the Maintenance/Test
Analog Port when the test is requested.
Table 9-440. TEST #963 Analog Port Sanity Test
Error
Code Test Result Description/ Recommendation
2000 ABORT Response to the test request was not received within the allowable time
period.
2100 ABORT System resources required to run this test are not available.
2500 ABORT An internal operation failed; the test could not be completed.
1. Retry the command at 1-minute intervals a maximum of 3 times.
50 FAIL The switch was unable to communicate with the port circuitry used for
analog trunk testing.
1. Reset the circuit pack via the busyout board UUCSS, reset board
UUCSS, release board UUCSS command sequence.
2. Test the port again via the test port UUCSS01 l command.
3. If the test fails again, replace the circuit pack.
PASS The Maintenance/Test Analog Port analog trunk testing capability is
operating correctly.
Continued on next page