Using a certified and high accuracy millivolt simulator, generate a millivolt signal to
the T/C electrical connection on the front panel (nominal value is the recommended
value for the calibration): pressing the ent key causes the microprocessor to
combine the millivolt values (true value and effective reading).
Calibration of the Volt input range (DBC-TC only)
From the CALIBRATION display, select V INPUT using the keys and press
ent.
Using a certified and high accuracy Volt simulator, apply the calibration signal to the
Voltage electrical connection on the front panel of the instrument (the nominal value
is the recommended value for the test).
Pressing the ent key causes the microprocessor to combine the voltages indication
(True value and Reading).
Calibration of the mA input range (DBC-TC only)
From the CALIBRATION display, select mA INPUT using the keys and press
ent.
Using a traceable and high accuracy mA simulator, generate a specific current
value to the related electrical connection on the front panel of the instrument (the
mV (1)
V INPUT
mA INPUT