Chapter 4 Connect the Kinetix 350 Drive System
If the entire channel is constructed of stranded cable (no fixed cable), then this is
the equation for calculating maximum length:
Maximum Length = (113-2N)/y, meters
where N = the number of connections in the channel
and y = the loss factor compared to fixed cable (typically 1.2…1.5).
Figure 43 - CompactLogix Ethernet Port Location
The Port 1 Ethernet connection is used for connecting to a Logix5000 controller
and configuring your Kinetix 350 drive.
Figure 44 - Ethernet Wiring Example - External Switch
The Ethernet ports are on
bottom of controller.