Alliance Laundry Systems Stacked Clothes Dryer Washer/Dryer User Manual


 
© Copyright, Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT
Installation
510975
22
Electrical Requirements
(Electric Dryers)
(120/240 Volt, 60 Hertz, 3-Wire Installation)
(120/208 Volt, 60 Hertz, 3-Wire Installation)
NOTE: The wiring diagram is located behind the
control panel, inside the control cabinet.
Grounding and Wiring Instructions
Each dryer must be connected to a grounded
metal, permanent wiring system; or an
equipment-grounding conductor must be run
with the circuit conductors and connected to the
equipment-grounding terminal or lead on each
dryer.
Each dryer has its own terminal block that must
be connected to a separate branch, 60 Hertz,
single phase circuit, AC (alternating current)
circuit, fused at 30 Amperes (the circuit must be
fused on both sides of the line). ELECTRICAL
SERVICE FOR THE DRYER UNIT
SHOULD BE OF MAXIMUM RATED
VOLTAGE LISTED ON THE NAMEPLATE.
DO NOT CONNECT DRYER TO 110, 115,
OR 120 VOLT CIRCUIT. Heating elements are
available for field installation in dryer units
which are to be connected to electrical service of
different voltage than that listed on nameplate,
such as 208 Volt.
If branch circuit to dryer unit is 15 feet (4.5 m) or
less in length, use U.L. (Underwriters
Laboratories) listed No. 10 A.W.G. wire (copper
wire only), or as required by local codes. If over
15 feet (4.5 m), use U.L. listed No. 8 A.W.G.
wire (copper wire only), or as required by local
codes. Allow sufficient slack in wiring so dryer
can be moved from its normal location when
necessary.
The power cord (pigtail) connection between
wall receptacle and dryer unit terminal block is
NOT supplied with dryer unit. Type of pigtail
and gauge of wire must conform to local codes
and with instructions mentioned on the following
pages.
The method of wiring the dryer unit is optional and
subject to local code requirements. Refer to Figure 13.
To reduce the risk of fire, electric shock or
personal injury, all wiring and grounding
MUST conform with the latest edition of
the National Electrical Code ANSI/NFPA
70 or the Canadian Electrical Code, CSA
C22.1, and such local regulations as
might apply. It is the customers
responsibility to have the wiring and
fuses checked by a qualified electrician to
make sure the laundry room has adequate
electrical power to operate the dryer.
W035
WARNING