Dryer exhaust duct should enter the main duct at an
angle of no more than 30
° pointing in the direction of
the air flow. Ducts entering the main duct from
opposite sides should be staggered so as not to oppose
each other. See illustration below.
Provisions should be made for periodic lint removal
and cleaning of the main collector duct.
The outside end of the main duct should have a weather
hood (with hinged dampers) installed to prevent
passage of weather elements, insects, dust, and dirt into
the dryer.
If a weather hood cannot be used, the outside end of the
main duct should have a sweep elbow installed, and be
directed downward as shown on the following page. If
the main duct travels vertically through a roof rather
than through a wall, install 180
° sweep elbow on the
end of the duct with outlet at least 24 inches (61 cm)
above the highest part of the building.
Sufficient make-up air must be supplied to replace air
exhausted from dryer.
NOTE: Where the exhaust duct pierces the wall or
ceiling, an opening having a diameter of 4 inches (10.2
cm) larger than the diameter of the exhaust duct shall
be provided, and the exhaust duct centered within the
opening.
Damper, Part No. 58786, should be installed in dryer’s
exhaust system. This will prevent a backdraft when
dryer is not in use, and will keep the exhaust air in
balance within the central exhaust system.
IMPORTANT: Provisions must be made for make-up
air.
IMPORTANT: If several dryers are exhausted into a
main collector duct, it is essential that ductwork be
adequate in size and properly constructed for efficient
operation.
DRYER EXHAUST DUCT
DRYER EXHAUST DUCT
DRYER EXHAUST DUCT
DRYER EXHAUST DUCT
AIR FLOW MAIN COLLECTOR DUCT
30° 30°
30°
D026IE3A
30°
To reduce the risk of fire and the
accumulation of combustion gases, DO NOT
exhaust dryer air into a window well, gas
vent, chimney or enclosed, unventilated area,
such as an attic, wall, ceiling, crawl space
under a building or concealed space of a
building.
W045
WARNING