SSI America 9210 Washer/Dryer User Manual


 
M4557 - Model 9210 Nitriding Controller
SSi Manual SERIES 9210-M4557-Nitriding Page 32 of 32
IP Address Mask 3 255
IP Address Mask 4 0
IP Address Gateway 1 192
IP Address Gateway 2 168
IP Address Gateway 3 1
IP Address Gateway 4 1
Highlighting the parameter that needs to be entered and pressing the Enter button displays a numeric
keypad that can be used to enter the required value. This will range from 0 to 256.
The default IP address is: 192.168.0.200
The default IP Address Gateway is: 192.168.1.1
Pressing the Esc key returns you to the configuration menu.
Event Control
This menu option will allow the user to set up the
event control for the 9210. The “Hold Instrument
Number” selection will display a numeric keypad
that can range from 0 to 11. The “Hold Minimum
PV” selection will display a numeric keypad that
will range from 0 to 4000. The “Hold Maximum
PV” selection will display a numeric keypad that
will range from 0 to 4000. The “Event for
Program Run” selection will display a numeric
keypad that will range from –1 to 15. A value of
1 means there is no event. The “Event for
Program Reset” selection will display a numeric
keypad that will range from –1 to 15. A value of
1 means there is no event. The “Event 0” through
“Event 15” selection will allow the user to assign
the specific events. The list of options for this
selection is:
Event Inactive
Event Active, Open Triggers Hold
Event Active, Closed Triggers Hold
Valve Configuration
This screen provides setup information for the 9210
on the flow controller boards.
The “Decimal Place” selection determines how the
9210 will display gas flows. This will display a
numeric keypad that can range from 0 to 4.
The “Valve Control Mode” selection determines how
the 9210 will adjust gas flows if required for
%Dissociation. This will display a screen that will
allow the user to select the mode. The choices are:
Individual Trim
Flow
Ratio
Auto
The “D.A. Switch Point” selection determines the
control switch point for switching the atmosphere display from %Dissociation to Kn. This will display a