Speed Queen TMB796C Washer User Manual


 
Electrical Requirements
M414905
46
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
50 and 75 Pound Electric Models
Refer to Table 10.
NOTE: Wire size and breaker ratings were
obtained from the Canadian Electrical Code for
75 C. wire and are intended for use as a guideline
only. Electrical connections should be made by a
qualified electrical contractor in accordance with
all applicable local and national requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).
Serial Plate Rating
Terminal Block
Connections
Required
Serial Plate Amps Recommended Circuit
Nonreversing Reversing
Breaker
Rating
Wire Size
AWG (mm
2
)
240V/50Hz/1ph
(50 Pound only)
L1, Neutral and Ground 93 95 125A – 1 pole 1 (42.4)
200-208V/60Hz/3ph
L1, L2, L3 and ground 89 88 125A – 3 pole 1 (42.4)
200V/50Hz/3ph
L1, L2, L3 and ground 84 85 125A – 3 pole 1 (42.4)
230V/50Hz/3ph
L1, L2, L3 and ground 73 75 100A – 3 pole 3 (26.7)
240V/50Hz/3ph
L1, L2, L3 and ground 79 78 100A – 3 pole 3 (26.7)
240V/60Hz/3ph
L1, L2, L3 and ground 79 78 100A – 3 pole 3 (26.7)
380V/50 or 60Hz/3ph
L1, L2, L3 and ground 47 48 60A – 3 pole 6 (13.3)
400-415V/50Hz/3ph
L1, L2, L3 and ground 43 44 60A – 3 pole 6 (13.3)
440V/60Hz/3ph
L1, L2, L3 and ground 41 41 51A – 3 pole 6 (13.3)
480V/60Hz/3ph
L1, L2, L3 and ground 38 38 50A – 3 pole 6 (13.3)
Table 10