Electrical Requirements
45
M414905
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
75 Pound Gas and Steam Models
Refer to Table 8 and Table 9.
NOTE: Wire size and breaker ratings were
obtained from the Canadian Electrical Code for
75 C. wire and are intended for use as a guideline
only. Electrical connections should be made by a
qualified electrical contractor in accordance with
all applicable local and national requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).
Serial Plate Rating
Terminal Block
Connections
Required
Serial Plate Amps Recommended Circuit
Nonreversing Reversing
Breaker
Rating
Wire Size
AWG (mm
2
)
120V/60Hz/1ph
L1, Neutral and ground 13.8 N/A 20A – 1 pole 12 (3.31)
200-208V/60Hz/1ph
L1, Neutral and ground 7.6 N/A 15A – 1 pole 14 (2.08)
200-208-240V/60Hz/
1ph
L1, L2 and ground 7.6 N/A 15A – 2 pole 14 (2.08)
230-240V/50Hz/1ph
L1, Neutral and ground 6.7 7.0 15A – 1 pole 14 (2.08)
200-208V/60Hz/3ph
L1, L2, L3 and ground 3.8 4.3 10A – 3 pole 14 (2.08)
200V/50Hz/3ph
L1, L2, L3 and ground 3.5 4.5 10A – 3 pole 14 (2.08)
240V/60Hz/3ph
L1, L2, L3 and ground 3.8 4.3 10A – 3 pole 14 (2.08)
230-240V/50Hz/3ph
L1, L2, L3 and ground 3.5 4.9 10A – 3 pole 14 (2.08)
380V/50 or 60Hz/3ph
L1, L2, L3 and ground 1.8 2.1 10A – 3 pole 14 (2.08)
400-415V/50Hz/3ph
L1, L2, L3 and ground 1.8 2.1 10A – 3 pole 14 (2.08)
440V/60Hz/3ph
L1, L2, L3 and ground 1.9 2.1 10A – 3 pole 14 (2.08)
460-480V/60Hz/3ph
L1, L2, L3 and ground 1.9 2.1 10A – 3 pole 14 (2.08)
N/A = Not Applicable
Table 8
F75 Gas Models Only
Serial Plate Rating
Terminal Block
Connections
Required
Serial Plate Amps Recommended Circuit
Nonreversing Reversing
Breaker
Rating
Wire Size
AWG (mm
2
)
200-208V/60Hz/3ph
L1, L2, L3 and ground N/A 6.3 15A – 3 pole 14 (2.08)
240V/60Hz/3ph
L1, L2, L3 and ground N/A 6.3 15A – 3 pole 14 (2.08)
460-480V/60Hz/3ph
L1, L2, L3 and ground N/A 3.1 10A – 3 pole 14 (2.08)
N/A = Not Applicable
Table 9