American Dryer Corp. ML-410 Washer/Dryer User Manual


 
38
2.
Technical Gas Data
a. Gas Specifications
Refer to the illustration on page 12.
b. Gas Connections
Run a 2 (5.08 cm) gas pipe from the main gas header to the dryer. There is a 2 (5.08 cm) gas pipe
connection at the bottom of the dryer base.
Inlet Connection ----------- one (1) 2-inch F.P.T.
Btu/hr input (per dryer) --- 1,600,000 btu/hr - 403,200 kcal/hr
1) Natural Gas
Pressure regulation is controlled by both gas valves internal regulators. Incoming supply pressure
must be consistently between a minimum of 6.0 inches water column (W.C.) - 14.92 mb - and a
maximum of 10.5 inches water column (W.C.) - 26.1 mb.
2) Liquid Propane (L.P.) Gas
Dryers made for use with liquid propane (L.P.) gas have both of their gas valves internal pressure
regulators open so that the gas pressure must be regulated upstream of the dryer. The pressure is
measured at each gas valve pressure tap and must be a consistent 10.5 inches water column (W.C.)
- 26.1 mb. There is no regulator or regulation provided in an L.P. gas dryer. The water column must
be regulated at the source (L.P. tank) or external regulator/regulation must be added to each dryer.
Type of Gas
Natural Liquid Propane
Manifold Pressure* 3.5 inches W.C. 8.7 mb 10.5 inches W.C. 26.1 mb
Inline Pressure 6.0 inches W.C.
14.9 mb
10.5 inches W.C.
26.1 mb
Shaded areas are stated in metric equivalents
* Measured at gas valve pressure taps when the gas valves are on.