Programming
Note: Pressing the Start key while the test cycle is
in progress will immediately advance to the next
step in the test cycle. Drain and load balancing steps
may not be skipped.
The test cycle is as follows:
a. Once the Start key is pressed, the door
interlock is de-energized (preventing the
door from being opened), the drain valve
closes, the cylinder begins agitating at wash
speed, and both water inlet valves are
energized. The display alternately flashes
“bFIL” and “LO” (both hot and cold fill
valves on, filling to low level).
b. When the water level switch indicates that
low water level has been reached, the water
fill valves shut off and the dot above and to
the immediate left of the fourth digit of the
display lights.
c. The cold water fill valve is energized. The
display alternately flashes “CFIL” and
“Med” (cold fill valve on, filling to medium
water level).
d. When the water level switch indicates that
medium water level has been reached, the
cold water fill valve shuts off and the dot
above and to the immediate left of the third
digit of the display lights.
e. The hot water fill valve is energized. The
display alternately flashes “HFIL” and “HI”
(hot fill valve on, filling to high water level).
f. When the water level switch indicates that
high water level has been reached, the hot
water fill valve shuts off and the dot above
and to the immediate left of the second digit
of the display lights.
g. The auxiliary heat output is energized,
provided that the water level switch indicates
that at least low water level is present. The
cold water fill valve is energized. The supply
1 output is energized for five seconds. The
display alternately flashes “SUP1” and
“HEAt” (supply 1 output on, auxiliary heat
output on).
h. The supply 2 output is energized for five
seconds. The display alternately flashes
“SUP2” and “HEAt” (supply 2 output on,
auxiliary heat output on).
i. The supply 3 output is energized for five
seconds. The display alternately flashes
“SUP3” and “HEAt” (supply 3 output on,
auxiliary heat output on).
j. The auxiliary heat output is turned off. The
supply 4 output is energized for five seconds.
The display shows “SUP4” (supply 4 output
on).
k. The supply 5/auxiliary fill output energizes
for five seconds. If the “SUP5”/“AFIL”
setup option is set to “SUP5,” the display
shows “SUP5” (supply 5/auxiliary fill output
on). If the “SUP5”/“AFIL” setup option is
set to “AFIL,” the display shows “AFIL”
(supply 5/auxiliary fill output on).