Steam Requirements
M414038
44
© Copyright, Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT
170 Pound Tumblers
Figure 17
T497I
NOTE: Sizing of pipe diameters is shown for steam at rated pressure of 120 psi. Pipe diameter needs to be increased
accordingly if pressure is less than 125 psi (refer to Table 9). Piping must also be sized accordingly for length of runs
and number of elbows.
1 Risers 12 in.
(305 mm) 6 18 in. Drop (457 mm)
2 Shut-Off Valve 7 Steam Bonnet
3 Check Valve 8 Solenoid Valve (Supplied with machine)
4 Vacuum Breaker 9 Union
5 Condensate Return Line from Supply Line 10 Trap with Built-In Strainer
SUPPLY
2
1
9
3
RETURN
2
3
7
10
4
5
8
6
Model
Steam Pressure
(psi)
Minimum Pipe Diameter
Steam Trap Size
(Pounds Condensate/Hour)
170CSH 110 125 1 in. (25 mm) 517
170CSH 60 110 1.25 in. (32 mm) 517
170CSH 35 60 1.5 in.(38 mm) 517
Table 9