Alliance Laundry Systems T433I Clothes Dryer User Manual


 
Installation
M414038
18
© Copyright, Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT
Location Requirements
The tumbler must be installed on a level floor capable
of supporting 120 lbs./ft
2
(585.8 kg/m
2
). Floor
covering materials such as carpeting or tile should be
removed.
To assure compliance, consult local building code
requirements.
The tumbler MUST NOT be installed or stored in area
where it will be exposed to water and/or weather.
IMPORTANT: DO NOT block the airflow at the
rear of the tumbler with laundry or other articles.
Doing so would prevent adequate air supply to the
combustion chamber of the tumbler.
A typical tumbler enclosure is shown in Figure 1. Note
that the enclosure touches the tumbler top and side
panels. Also, note the minimum and maximum
dimensions. Local codes and ordinances must be
complied with.
IMPORTANT: Install tumblers with sufficient
clearance for servicing and operation. Refer to
Figure 1.
Figure 1
To reduce the risk of serious injury, install
lockable door(s) to prevent public access
to rear of tumblers.
W055
WARNING
TMB237N
NOTE: Shaded areas indicate adjacent structure.
1 Zero clearance permitted for first 4 in. (102 mm)
2 4 in. (102 mm)
3 Minimum clearance permitted for remainder: Gas 4 in. (102 mm), Steam 12 in. (305 mm)
4 Guard
5 Provision for Make-Up Air
6 24 in. (610 mm) Minimum, 36 in. (914 mm) recommended for maintenance purposes
7 Zero Clearance
3
1
4
5
6
7
2
WARNING
To reduce the risk of severe injury, clearance of tumbler cabinet from combustible
construction must conform to the minimum clearances.
W056