Alliance Laundry Systems 70269701R4 Clothes Dryer User Manual


 
Electrical Requirements
70269701
52
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Electrical Requirements for Gas and
Steam Models
Refer to Table 9 and Table 10.
NOTE: Minimum wire sizes are obtained from
Canadian Electrical Code Table 2 for 75°C
Conductors and are intended for use as a guideline
only. Electrical connections should be made only by
a qualified electrical contractor in accordance with
all applicable local and national requirements.
NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.
NOTE: Use copper conductors only.
NOTE: Connect to individual branch circuit.
NOTE: 3 Phase Only – Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).
For 25, 30 and 35 Pound Gas and Steam Models:
Table 9
Serial Plate
Voltage
Terminal Block
Connections
Required
Current
(Amps)
Recommended
Fuse or
Breaker Rating
(Amps)
Breaker
Poles
Recommended
Minimum
Conductor Size
[AWG (mm
2
)]
120V/60Hz/1ph
L1, Neutral,
and ground
12.0 15 1 14 (2.08)
208-240V/60Hz/
1ph
L1, L2, Neutral,
and ground
6.7 10 2 14 (2.08)
120V/60Hz/1ph
L1, Neutral,
and ground
7.5** 10 1 14 (2.08)
208-240V/60Hz/
1ph
L1, L2, Neutral,
and ground
4.5** 10 2 14 (2.08)
100V/60Hz/1ph
L1, Neutral,
and ground
11.0 15 1 14 (2.08)
200-220V/60Hz/
1ph
L1, Neutral,
and ground
5.8 10 1 14 (2.08)
100V/50Hz/1ph
L1, Neutral,
and ground
12.1 20 1 12 (3.31)
200V/50Hz/1ph
L1, Neutral,
and ground
7.5 10 1 14 (2.08)
230-240V/50Hz/
1ph
L1, Neutral,
and ground
7.5 10 1 14 (2.08)
200-208V/60Hz/
3ph
L1, L2, L3,
and ground
3.2 10* 3 14 (2.08)
240V/60Hz/3ph
L1, L2, L3,
and ground
3.2 10* 3 14 (2.08)
200V/50Hz/3ph
L1, L2, L3,
and ground
2.9 10* 3 14 (2.08)
230-240V/50Hz/
3ph
L1, L2, L3,
and ground
3.5 10* 3 14 (2.08)
380V/50Hz/3ph
L1, L2, L3,
and ground
1.5 10* 3 14 (2.08)
400-415V/50Hz/
3ph
L1, L2, L3,
and ground
1.6 10* 3 14 (2.08)
460-480V/60Hz/
3ph
L1, L2, L3,
and ground
1.6 10* 3 14 (2.08)
* 3 Phase machines should not have fuses, breakers only.
** Special low Amp blower model, 25 Pound only