Whirlpool 3390148 Clothes Dryer User Manual


 
Exhaust
reqdrements
Exhaust materials are not
supplied.
Fire Hazard
l
Do Not use non-metal, flexible
duct.
l
Do Not use metal duct smaller
than four Inches in diameter.
l
Do Not use exhaust hoods with
magnetic latches. Improper air
supply for exhaustlng may
result in a fire.
l
Check that exhaust system is
not longer ttian specified.
Exhaust systems longer than
specified will:
- Accumulate Ilnt.
- Shorten the life of the product.
- Reduce performance,
resulting In longer drying
times and Increased energy
usage.
Failure to follow spectfications-,
may result In a fire.
l
Dryers must be exhausted to
the outside.
l
Do Not exhaust dryers into
chimney, furnace cold air duct,
attlc or crawl space, or any
other duct used for venting.
l
Clean the exhaust system
frequently.
l
Do Not Install flexible duct
under wall, ceiling or floor
materials.
Accumulated lint could result in
fire or cause moisture damage.
Use duct tape to
seal all joints.
good
better
exhaust airflow
exhaust oifflow
Four-inch metal exhaust duct is
required. Plan installation- to use
the fewest number of elbows and
turns.
Page 6
Metal flexible duct mus be fully
extended and supports d when
the dryers are In final pc sit-ion. DO
NOT KINK OR CRUSH TH1’ DUCT. The
metal flexlble duct mus be
completely opeti to allc IW
adequate exhaust air tc B flow.
Allow as much room as possible
when using elbows or rr aking turns.
Bend duct gradually to avold
kinklng. Remove 8x1~s:; flexible duct
to bvold sagging and ki nklng that
may cause reduced alr low.
The exhaust duck can t = routed up.
down, left, right or strais ht out the
back
of the dryers. The lower dryer
can also be exhausted hrough the
bottom of the dryer. Prc Iduct
dimensions and recesse 3 area
requirements are glven Dn Page 9.
For exhaust systems not covered
by the exhaust length cl )art. see
WhIrlwool Service Manuc &
‘Exhausting WhIrlpool Dryers’, Part
No. 603197, available fit m your
Whlrlpool parts diitributc r.
Rear Exhaust: The maxim urn length
of the exhaust system dc !pends on
the type of duct, the nul nber of
elbows, and the type of exhaust
hood. The maximum ler gth for both
rigld and flexlble duct is : hewn in
the chart.
Aps@%!
A’
A’
lumber of
0”
turns
Exhaust
Hood T rpe
A
43 Ft.
33 Ft.
23 Ft.
30 Ft.
24 Ft.
16 Ft.
Maxlmum
length of
4
dia. rigid
metal duel
Maximum
length of 4
dia. flexibl
metal due
Side or Bottom Exhaust: The
maxlmum length of the exhaust
system If dryer is exhausted out the
side or bottom is 16 feet with two
external elbows and hood.
Service check: The back pressure In
any exhaust system used must not
exceed 0.6 Inches of water column
measured with an inclined
manometer at the point that the
exhaust system connects to the
dryers.
If the dryers are installed in a
confined area, they must be
exhausted to the outside and
provislon must be made for
enough air for combustion and
ventilation. Check governlng
codes and ordinances. Also refer.
to the ‘Recessed area and closet
installation instructions.’ Page 9.
An exhaust hood should cap the
exhaust duct to prevent exhausted
air from returnlng into the dryers.
The outlet hood must be at least 12
inches from the ground or any
object that may be In the path of
the exhaust.
A main exhaust duct can be used
for exhausting a group of dryers.
Main exhaust duct should be sized
to remove 200 CFM of alr per
dryer. Large-capacity lint screens
of proper design may be used In
the main exhaust duct if checked
and cleaned frequently. The room
where the dryers are located
.
should have make-up air equal to
or greater than the CFM of all the
dryers in the room.
air flow
1 main collector dud
Back-drafl damper kits (Part No.
3391910) are avallable from your
Whirlpool dealer and should be
installed in each dryer’s exhaust
duct to prevent exhausted air
from returning into. the dryers and
tb keep the exhaust in balance
within the Fain exhaust duct.
Unobstructed air openlngs are
required.