American Dryer Corp. Super AD-50 Clothes Dryer User Manual


 
15
MULTIPLE DRYER (Common) VENTING
If it is not feasible to provide separate exhaust ducts for each dryer, ducts for individual dryers may be channeled
into a common main duct. Each dryer is provided with a back draft damper. The individual ducts should enter the
bottom or side of the main duct at an angle not more than 45° in the direction of the airflow.
The main common duct may be any shape so long as the minimum cross-sectional area is provided. The main
duct should be tapered with the diameter increasing before each individual 10-inch duct is added (refer to Illus.
C below).
Illus. C