19
2. Electrical Service Specifications
a. Gas and Steam Models ONLY
IMPORTANT: Figures shown are for Non-Reversing Models ONLY. For reversing models contact
the factory.
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the back side of the upper/top control door. In the case of 208 VAC or
230/240 VAC, the supply voltage must match the electric service specifications of
the data label exactly.
IMPORTANT: The wire size must be properly sized to handle the related current.
WARNING: 208 VAC and 230/240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or
obligation.
EURO-35 (GAS)
EURO-35 (STEAM)
IMPORTANT: 208 VAC and 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker
size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3Ø dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
FUSING
Dual Element
Time Delay
CIRCUIT
BREAKER
120 2 13 #10 20 20
208 2 8 #14 12 15
208 3/4 5 #14 8 15
230 2 7 #14 12 15
230 3/4 5 #14 8 15
240 2 7 #14 12 15
380/400 3/4 3 #14 5 15
416 3/4 3 #14 5 15
460 3/4 3 #14 5 15
* AWG Stranded Wire ... for individual lengths less than 100 feet (30.48 m).