American Dryer Corp. EURO-35 Clothes Dryer User Manual


 
9
B. LOCATION REQUIREMENTS
Before installing the dryer, be sure the location conforms to local and national codes and ordinances.
1. The dryer must be installed on a sound level floor capable of supporting its weight. It is recommended that
carpeting be removed from the floor area that the dryer is to rest on.
2. The dryer must not be installed or stored in an area where it will be exposed to water and/or weather.
3. The dryer is for use in noncombustible locations.
4. Provisions for adequate air supply must be provided as noted in this manual (refer to Fresh Air Supply in
Section D).
5. Clearance provisions must be made from combustible construction as noted in this manual (refer to Dryer
Enclosure Requirements in Section C).
6. Provisions must be made for adequate clearances for servicing and for operation as noted in this manual
(refer to Dryer Enclosure Requirements in Section C).
7. Dryer must be exhausted to the outdoors (refer to Exhaust Requirements in Section E).
8. Dryer must be located in an area where correct exhaust venting can be achieved as noted in the manual
(refer to Exhaust Requirements in Section E).
IMPORTANT: Dryer should be located where a minimum amount of exhaust duct will be necessary.