American Dryer Corp. AD-75V Clothes Dryer User Manual


 
113231-4 www.amdry.com 17
ELECTRIC
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
When fuses are used they must be dual element, time delay, current limiting, class RK1 or RK5 ONLY.
Calculate/determine correct fuse value, by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size
according to appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz 50 Hz
30 kW
208 3 91 * 125 125
230 3 83 * 125 125
240 3 79 * 100 100
380 3 48 * 60 60
380 4** 54 * 70 70
400 4** 51 * 70 70
416 4** 50 * 70 70
460 3 40 * 50 50
480 3 39 * 50 50
575 3 33 * 50 50
36 kW
208 3 3 108 * 150 150
230 3 3 98 * 125 125
240 3 3 94 * 125 125
380 3 3 58 * 80 80
380 3 4** 63 * 80 80
400 3 4** 60 * 80 80
416 3 4** 58 * 80 80
460 3 3 48 * 60 60
480 3 3 46 * 60 60
b. Electric Models Only
ALL electrically heated dryers must be connected to the electric service shown on the data label. The
connecting wires must be properly sized to handle the rated current.
* AWG Stranded Wire Type – size wire as per National Electrical Code or local codes. 8/1/05
** 3-Wire available.
3. Grounding
A ground (earth) connection must be provided and installed in accordance with state and local codes. In
the absence of these codes, grounding must conform to applicable requirements of the National Electrical
Code ANSI/NFPA NO. 70-LATEST EDITION, or in Canada, the installation must conform to applicable
Canada Standards: Canadian Electrical Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION. The
ground connection may be to a proven earth ground at the service breaker panel.
For added personal safety, when possible, it is suggested that a separate ground wire (no. 18 minimum) be
connected from the ground connection of the dryer to a grounded cold water pipe. DO NOT ground to a
gas pipe or hot water pipe. The grounded cold water pipe must have metal-to-metal connection
ALL the
way to the electrical ground. If there are any nonmetallic interruptions, such as, a meter, pump, plastic,
rubber, or other insulating connectors, they must be jumped out with no. 4 copper wire and securely
clamped to bare metal at both ends.
IMPORTANT: For personal safety and proper operation, the dryer must be grounded.
Provisions are made for ground connection in each dryer at the electrical service connection area.