A SERVICE OF

logo

SECTION 3: WIRING AND INSTALLATION DS2100 User's Manual (Preliminary)
PAGE 3-31
3.7.1.4 Size D
EMC Filter,
Fuses etc.
See
Section 2
Installation
4 5 6
L1 L2 L3
Connector J9
D
3
PE
a.c. Mains
L1
L2
L3
Protective
Earth
Figure 3.18 Size D AC Mains Input Connection
- Fixed connector: 4 pole, screw terminal
- D size wiring: cable 6 AWG (13 mm
2
) for 50/140
- D size wiring: cable 4 AWG ( 21mm
2
) for 60/180
- PE Terminal wiring: cable 6 AWG (13 mm
2
) for 50/140
- PE Terminal wiring: cable 4 AWG (21 mm
2
) for 60/180
- Stripping Length 16mm
- Tightening Torque: 2-2.3Nm
Pos.
Name
Function
J9.3 PE Protective Earth Screw Terminal
J9.4 L1
Phase "L1", three-phase voltage input 230/460Vac ±10%
J9.5 L2
Phase "L2", ", three-phase voltage input 230/460Vac ±10%
J9.6 L3
Phase "L3", ", three-phase voltage input 230/460Vac ±10%
Table 3.6 J9 AC Mains Power connector, D Size
3.7.2 Softstart & Power Cycling Frequency Limits
The DS2100 contain an internal soft-start function. The soft-start function limits the inrush current into the DS2100's
D.C. Bus smoothing capacitors after the a.c. mains has been switched on.
If the frequency of power cycling becomes too high, then the power dissipation in the soft-start resistor can be excessive.
In this case the softstart circuitry may become damaged.
CAUTION:- The internal softstart resistors are designed to allow an AC application o
f
once every 60 seconds. If this rate is exceeded, then the internal softstart resistors may
be damaged.