Installing Steam Trap and Making
Condensate Return Connections
The steam trap must be installed and the coil outlet
connections must be connected to the condensate
return lines. The following steps outline the procedure
for installing the steam trap and connecting the
condensate return lines. Refer to
Figure 15 for typical
installations.
1. Connect a flexible hose to each steam coil outlet.
2. Install a strainer to the ends of each flexible hose.
3. Install a steam trap to each strainer.
IMPORTANT: Steam trap must be installed a
minimum of 18 inches (457 mm) below the steam
coil outlet connections.
4. Install a globe shut-off valve to each steam trap.
5. Connect to the condensate return lines.
WARNING
The flexible steam hoses connecting the
coil outlet connections and steam traps
must have a minimum of 125 psig
(pounds per square inch gauge) (8.79 kg/
sq. cm.) working pressure. A shut-off
valve must be installed downstream from
each steam trap so the condensate return
line can be isolated in event a steam trap
requires maintenance.
Each steam trap must be supported so
minimum load is exerted on the coil outlet
connection.
W066