Exhaust Requirements
70256801
32
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Figure 12
T472I
1 NOTE: Where the exhaust duct pierces a combustible wall or ceiling, the opening must be sized per local codes.
2 Outlet Duct Diameter for One Battery Same as Largest Station Used
3 Outlet Duct Diameter for Two Batteries
4 45° Typical
LKJ I HG F E D CB A
L
3
4
1
2
D1
D2
Duct
Station
8 Inch Duct 10 Inch Duct
50, 75 Pound 634
D1 D2 D1 D2
A 10 in. (254 mm) 13 in. (330 mm) 10 in. (254 mm) 15 in. (381 mm)
B 12 in. (305 mm) 17 in. (432 mm) 15 in. (381 mm) 22 in. (559 mm)
C 15 in. (381 mm) 18 in. (457 mm) 18 in. (457 mm) 26 in. (660 mm)
D 17 in. (432 mm) 24 in. (610 mm) 21 in. (533 mm) 30 in. (762 mm)
E 19 in. (483 mm) 27 in. (686 mm) 24 in. (610 mm) 34 in. (864 mm)
F 21 in. (533 mm) 30 in. (762 mm) 26 in. (660 mm) 37 in. (940 mm)
G 23 in. (584 mm) 33 in. (838 mm) 28 in. (711 mm) 40 in. (1016 mm)
H 25 in. (635 mm) 34 in. (864 mm) 30 in. (762 mm) 43 in. (1092 mm)
I 26 in. (660 mm) 37 in. (940 mm) 32 in. (813 mm) 46 in. (1168 mm)
J 27 in. (686 mm) 39 in. (991 mm) 33 in. (838 mm) 47 in. (1194 mm)
K 29 in. (737 mm) 40 in. (1016 mm) 35 in. (889 mm) 50 in. (1270 mm)
L 30 in. (762 mm) 42 in. (1067 mm) 36 in. (914 mm) 51 in. (1295 mm)
Table 8