American Dryer Corp. ADS-464 II Clothes Dryer User Manual


 
69
Release the REVERSE Push-button
Does PLC (Programmable Logic Controller) input L.E.D. #18 go OFF?
If the answers to these questions are YES, wiring to the PLC is correct.
If any answer to these questions is NO, refer to Probable Causes below
Tumbler Forward Switch --- PB1
For quick check of the wiring of PB1 to the PLC (Programmable Logic Controller) perform the following
test with the control voltage ON (green button).
Press the FORWARD Push-button.
Does PLC (Programmable Logic Controller) input L.E.D. #17 light?
Release the REVERSE Push-button.
Does PLC (Programmable Logic Controller) input L.E.D. #17 go OFF?
If the answer to these questions are YES, wiring to the PLC (Programmable Logic Controller) is
correct.
If the answer to these questions are NO, refer to Probable Causes below
a. PROBABLE CAUSES;
1) FUSE 4 ON MAIN ELECTRICAL PANEL
2) FAULTY SWITCHES
3) WIRING BACK TO PLC (Programmable Logic Controller)
b. POSSIBLE SOLUTIONS;
1) Check fuse blown indicator on fuse 4; replace fuse, if necessary and retest.
2) Check switches using an OHM meter; replace if necessary, and retest.
3) Refer to ADS-464 Pendant associated wiring diagrams for detailed assembly and wiring information.
Check
ALL circuits back to PLC (Programmable Logic Controller).
ADS-464 PENDANT ASSEMBLY DIAGRAM
ADS-464 ANNUNCIATOR, PENDANT, and UPPER RTDS (Resistive Temperature Device)
WIRING DIAGRAM
EMERGENCY STOP (E-Stop) SWITCH --- PB6
If the EMERGENCY STOP (E-Stop) switch (pendant) does not respond: