American Dryer Corp. ADS-464 II Clothes Dryer User Manual


 
68
TUMBLER FORWARD PENDANT --- PB1
This push button comprises of one (1) normally open switch, and is mechanically interlock with Tumbler
Reverse Push Button.
EMERGENCY STOP (E-Stop) PENDANT --- PB6
This push button switch is normally an open device and its function is to shut down the control voltage to
the dryer in the event it is pressed.
NOTE: It WILL NOT effect the sprinkler circuit power.
2.0 Verify Pendant Electrical Signals
ALL the pendant control signals are interfaced to the Main Electrical Panels PLC (Programmable Logic
Controller) except for EMERGENCY STOP (E-Stop).
LOAD - Level - UNLOAD Switch --------- A and B
Tumbler Reverse Switch----------------------- PB2
Tumbler Forward Switch ---------------------- PB1
EMERGENCY STOP (E-Stop) Switch -- PB6
For a quick check of the wiring of SEL 1 and 2 to the PLC (Programmable Logic Controller) perform the
following test with the control voltage ON (green button).
Turn the selector switch to LOAD
Does PLC (Programmable Logic Controller) input L.E.D. #15 light?
Turn the selector switch to UNLOAD
Does PLC (Programmable Logic Controller) input #16 light?
Turn the selector switch to LEVEL
Are both PLC (Programmable Logic Controller) input #15 and input #16 OFF?
If the answers to these questions are YES, wiring to the PLC (Programmable Logic Controller)
is correct
If any answer to these questions is NO, refer to Probable Causes paragraph on page 69.
Tumbler Reverse Switch --- PB2
For a quick check of the wiring of PB2 to the PLC perform the following test with control voltage
ON (GREEN button).
Press the REVERSE Push-button.
Does PLC (Programmable Logic Controller) input L.E.D. (light emitting diode) #18 light?