American Dryer Corp. ADS-464 II Clothes Dryer User Manual


 
58
3b) Wiring from the EMERGENCY STOP (E-Stop) button to the main electrical enclosure is faulty or
incorrect.
Check REAR PANEL CONTROLS WIRING DIAGRAM
Check TUMBLER JUNCTION BOX WIRING DIAGRAM
 Refer to section #3 on page 57 and retest
Drum Forward and Reverse Function
c. PROBABLE CAUSES;
1) Rear panel disconnect plug
2) Defective switches
3) Wiring back to the main electrical enclosure
d. POSSIBLE SOLUTIONS;
1) If either the Drum forward or reverse functions (rear) do not respond
Verify that the rear panel controls disconnect plug is indeed connected. This disconnect plug
allows for the removal of the rear control panel for dryer servicing
2) Defective Forward and Reverse Switch
Shut power off at the main breaker and remove the rear panel and check switches using an
OHM meter; replace if defective
Retest
3) Wiring Back to Main Electrical Enclosure
With the control voltage ON front panel green button
Select 1 on the O UNLOAD 1 switch located on the rear controls panel
Have someone PRESS either the forward or reverse buttons while you watch the input L.E.D.s
(light emitting diodes) of the programmable controller. Do the associated L.E.D.s light?
PLC PIN 20 = DRUM FWD., REAR PANEL
PLC PIN 21 = DRUM REV., REAR PANEL
If YES, refer to section #3a
If NO, refer to section #3b