20 American Dryer Corp. 113409-2
2. Electrical Service Specifications
a. Gas Models Only
Gas
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse value,
by applying either local and/or National Electrical Codes to listed
appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type ONLY.
For others, calculate/verify correct breaker size according to appliance
amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz 50 Hz
208 3ø 3 28.3 — 50
240 3ø 3 26.7 — 45
230 3ø 3 — 31.9 50
380 3ø 3
16.2
—25
380 3ø
4*
—16.1 25
400 3ø
4*
—16.1 25
416 3ø
4*
—16.0 25
440 3ø 3 14.4 — 20
460 3ø 3 13.9 — 20
480 3ø 3 13.9 — 20
575 3ø 3 11.4 — 20
* 3-Wire is available. 6/11/08