Installation
33
F232102
The power cable should be disconnected by one of two
methods. Either a plug socket combination that is
interlocked with a combined switch or a fixed
disconnect that provides relief from mechanical strain
on connection points should be used. Both methods
must comply with the authority having jurisdiction at
the point of installation and/or the National Electric
Code, article 400-5, EN60204 section 15.4.3. The
service disconnect mechanism should be between
2 and 6 feet (0.6 to 1.9 m) above the floor and should
be easily accessible.
Cabinet Freestanding
Electrical Specifications
Voltage Designation Standard Electric Heat
Model
Code
Voltage
Cycle
Phase
Wire
Full Load
Amps
Circuit
Breaker
A.W.G.
mm
2
Full Load
Amps
Circuit
Breaker
A.W.G.
mm
2
135
N440 480 50-60 3 3 15 30 10 3x4 78 95 4 3x25
P380 415 50-60 3 3 15 30 10 3x4 78 95 4 3x25
Q200 240 50-60 3 3 29 60 6 3x16 N/A
250
N440 480 50-60 3 3 28 40 8 3x10 N/A
P380 415 50-60 3 3 32 40 8 3x10 N/A
Q200 240 50-60 3 3 56 70 6 3x16 N/A
NOTE: Wire sizes shown are for copper, THHN, 90° conductor per NEC article 310.
Table 6