System Warranty
This equipment is designed to operate properly and produce
rated capacity when installed in accordance with accepted
industry standards.
Failure to meet the following conditions may result in voiding
of the system warranty:
System piping must be installed following industry
standards for good piping practices.
Inert gas must be charged into piping during welding.
System must be thoroughly leak-checked and evacuated
before initial charging. High vacuum gauge capable of
reading microns is mandatory. Dial indicating pressure
gauges are not acceptable.
All controls and safety switch circuits properly connected
per wiring diagram.
Factory-installed wiring must not be changed without
written factory approval.
Power supply to the system must meet the following
conditions:
Voltage for 208/230 motors not less than 185 volts or
more than 253 volts. For 460 motor, not less than 414
or greater than 506.
All other voltages must not exceed ±10 percent of
nameplate ratings.
Phase imbalance not to exceed 2 percent.
1.
2.
3.
4.
5.
6.
a.
b.
c.
In-Warranty Return Material Procedure
Material may not be returned except by permission of
authorized factory service personnel of Heatcraft Refrigeration
Products LLC in Stone Mountain, Georgia, USA. A Return Goods
tag will be sent to be included with the returned material. Enter
the information as called for on the tag in order to expedite
handling at our factories and prompt issuance of credits. All
parts shall be returned to the factory designated on the Return
Goods tag, transportation charges prepaid.
The return of a part does not constitute an order for replacement.
Therefore, a purchase order must be entered through your
nearest Heatcraft Refrigeration Products representative. The
order should include part number, model number and serial
number of the unit.
Remote Air-Cooled Condenser Installation and Operations Manual, August 2007 11