It is important that gas pressure regulators meet applicable pressure requirements and that gas meters be
rated for the total amount of
ALL the appliance BTUs being supplied.
IMPORTANT: The dryer and its individual shutoff valve must be disconnected from the gas supply
piping system during any pressure testing of that system at test pressures in excess of
1/2 psig (3.5 kPa).
NOTE: The dryer must be isolated from the gas supply piping system by closing its individual manual
shutoff valve during any pressure test of the gas supply system at test pressures equal to or
less than 1/2 psig (3.5 kPa).