American Dryer Corp. ML-145 Clothes Dryer User Manual


 
22
2.
Electrical Service Specifications
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the left inside front side panel (refer to the illustration on Section VII at
the upper right hand corner). In the case of 208 VAC or 230/240 VAC, the supply
voltage must match the electric service specifications of the data label exactly.
WARNING: 208 VAC and 230/240 VAC ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time without notice or
obligation.
MLG-145 (Gas)
MLS-145 (Steam)
ELECTRIC SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 230/240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES
: A. Fuse ratings are dual element, time delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct
breaker size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
FUSING
CIRCUIT
BREAKER
60 Hz 50 Hz
Dual Element
Time Delay
208 3 17 20 12 35 35
240 3 17 --- 12 35 35
380 3/4 --- 11 14 20 20
416 3/4 --- 10 14 15 20
460 3/4 9 --- 14 15 15
480 3/4 9 --- 14 15 15
* AWG Stranded Type Wire...for individual lengths less than 100 feet (31 meters).