American Dryer Corp. ML-145 Clothes Dryer User Manual


 
16
IMPORTANT: Exhaust back pressure measured by a manometer in the exhaust duct must not
exceed 0.3 inches of water column (W.C.) - 0.74 mb.
IMPORTANT: When the exhaust duct work passes through a wall, ceiling , or roof made of
combustible materials, the opening must be 2-inches (5.08 cm) larger than the duct
(ALL the way around). The duct must be centered within this opening.
a. Outside Duct Work Protection
1) To protect the outside end of horizontal duct work from the weather, a 90° elbow bent downward
should be installed where the exhaust exits the building. If the exhaust duct work travels vertically
up through the roof, it should be protected from the weather by using a 180° turn to point the
opening downward. In either case, allow at least twice the diameter of the duct between the duct
opening and the nearest obstruction.
IMPORTANT: DO NOT use screens or caps on the outside opening of the exhaust duct work.
2. Single Dryer Venting
Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct should
be laid out in such a way that the duct work travels as directly as possible to the outdoors with as few turns
as possible. It is suggested that the use of 90° turns in ducting be avoided; use 30° and/or 45° angles instead.
The shape of the exhaust duct work is not critical so long as the minimum cross section area is provided.
IMPORTANT: Minimum duct size for a dryer is 16-inches (40.64 cm) for a round duct or 14-1/2” x
14-1/2” (36.83 cm x 36.83 cm) for a square duct. THE DUCT SIZE MUST NOT
BE REDUCED ANYWHERE DOWNSTREAM OF THE DRYER.
IMPORTANT: Exhaust back pressure measured by a manometer at each basket (tumbler) exhaust
duct area must not exceed 0.3 inches of water column (0.74 mb).