American Dryer Corp. AD-310 Phase 7 Clothes Dryer User Manual


 
73
SECTION XIII
OPTIONAL SPRINKLER SYSTEM COMPONENTS
OPTIONAL SPRINKLER CIRCUIT COMPONENTS
AUTO “EMERGENCY STOP” (E-Stop) RELAY
This device, located in the front right electrical enclosure, supplies the main control voltage to the dryer.
The dryer’s sprinkler circuit supplies or removes 120 VAC to the coil of this relay for the “EMERGENCY
STOP” (E-Stop) power disconnect control.
TEMPERATURE CONTROLLER
This device is located in the front left electrical enclosure and monitors the sprinkler circuit temperature. Its
operating functions are preset at the factory and should not require any adjustment.
RESISTIVE TEMPERATURE DEVICE (RTD) TEMPERATURE PROBE
This device is a high temperature 100 ohm (100 W) RTD probe and is located on the upper left side of the basket
(tumbler).
PNEUMATIC VALVE
This is a dual pneumatic 110 VAC control valve and is located in the lower rear base section of the dryer. Power
to turn “ON” the pneumatic valve is supplied from the sprinkler control circuit. Power to turn “OFF” the sprinkler
is supplied from a manual reset button located on the right front control door.
SPRINKLER VALVE
This valve controls the flow of the sprinkler water. It is air actuated and requires air pressure to turn “ON” or
“OFF.”
NOTE THAT THERE IS A “RED” INDICATING PISTON AT THE REAR OF THIS SPRINKLER VALVE.
The piston indicates the current state of the valve; when the piston is “IN” the valve is “CLOSED,” when the
piston is “OUT” the valve is “OPEN.”
ALARM HORN
This component is an audible device to indicate that the sprinkler system has tripped and that water is flowing into
the basket (tumbler). The alarm horn will reset when the sprinkler system is reset.
SPRINKLER RESET BUTTON
This amber colored push button is located on the right hand control door and illuminates when the sprinkler system
is activated. Attempting to reset the sprinkler system with this button can be tried, however, if the sprinkler circuit
continues to be in the active mode the reset function will not latch.