Electrical Service Specifications
* AWG Stranded Type Wire ... for individual lengths less than 100 feet.
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that
is affixed to the back of the dryer, at the upper right hand corner. In the case of
208 VAC or 230/240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.
WARNING: 208 VAC and 230/240 Volts ARE NOT THE SAME. Any damage done to
dryer components due to improper voltage connections will automatically
VOID THE WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or
obligation.
ADG-170SE (Gas)
ADS-170SE (Steam)
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC
AND
230/240 VAC ARE NOT THE SAME. W
HEN
ORDERING
,
SPECIFY
EXACT
VOLTAGE
.
NOTE
: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct
breaker size according to appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz 50 Hz
60 Hz 50 Hz
208 3 29.6 --- 8 50 --- 60
230/240 3 27.4 --- 10 40 --- 60
380/400 3/4 --- 14.4 14 --- 20 25
416 3/4 --- 14.4 14 --- 20 25
460 3/4 14.8 --- 14 20 --- 25
575 3 11.4 --- 14 20 --- 20