American Dryer Corp. AD-115ES Clothes Dryer User Manual


 
28
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is
affixed to the back of the dryer, at the upper right hand corner. In the case of
208 VAC or 240 VAC, the supply voltage must match the electric service
specifications of the data label exactly.
WARNING: 208 VAC and 240 Volts ARE NOT THE SAME. Any damage done to dryer
components due to improper voltage connections will automatically VOID THE
WARRANTY.
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or
obligation.
ADE-115ES (60 Kw Electric Oven) Reversing, 3ø Motor
E
LECTRICAL
S
ERVICE
S
PECIFICATIONS
(
PER DRYER
)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
NOTES
: A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5 ONLY.
B. Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
C. Circuit breakers for 3Ø dryers must be 3-pole type.
OVEN SIZE
(Kw)
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
FUSING
CIRCUIT
BREAKER
Dual Element
Time Delay
60 Hz 50 Hz
60
208 3ø
3
-- 213 4/0 300 300
60 240 3ø
3
188 186 3/0 250 250
60 380 3ø
3
117 -- 1 150 150
60 380 3ø
4
117 -- 1 150 150
60 416 3ø
3
108 -- 2 150 150
60 416 3ø
4
108 -- 2 150 150
60 480 3ø
3
-- 97 3 150 125
60 480 3ø
4
-- 97 3 150 125
60 575/600 3ø 3/4 -- 78 4 100 110
* AWG Stranded Type Wire...for individual lengths less than 100 feet (31 meters).
(Motor Lead Wire is recommended.)