M414545
19
TUMBLER ENCLOSURE CONSTRUCTION
IMPORTANT: DO NOT block the airflow at the rear
of the tumbler with laundry or other articles. Doing
so would prevent adequate air supply to the
combustion chamber of the tumbler.
A typical tumbler enclosure is shown in Figure 2. Note
that the enclosure touches the tumbler top and side
panels. Also, note the minimum and maximum
dimensions. Be aware that there may be local codes and
ordinances which must be complied with.
IMPORTANT: Install tumblers with sufficient
clearance for servicing and operation. Refer to
Figure 2.
Figure 2
To reduce the risk of serious injury, install
lockable door(s) to prevent public access
to rear of tumblers.
W055
WARNING
0" CLEARANCE
NOTE: Shaded areas
indicate adjacent
structure.
0" CLEARANCE PERMITTED
FOR FIRST 4" (10.16 cm)
4" (10.16 cm)
MAXIMUM
12" (30.5 cm)
MINIMUM
CLEARANCE
PERMITTED
FOR REMAINDER
GUARD
24" (61 cm) MINIMUM
36" (91.4 cm) RECOMMENDED
FOR MAINTENANCE PURPOSES
PROVISION
FOR
MAKE-UP
AIR
T038IE3D
To reduce the risk of severe injury, clearance of tumbler cabinet from combustible
construction must conform to the minimum clearances.
W056
WARNING
Minimum Recommended Clearances
Model Top
First 4" (10.2 cm)
Top
(Remainder)
Back Sides
28" 0" (0.0 cm) 12" (30.5 cm) 24" (61 cm) 0" (0 cm)
31.5" 0" (0.0 cm) 12" (30.5 cm) 24" (61 cm) 0" (0 cm)