GE AV-300i Clothes Dryer User Manual


 
21
Control buttons
Jog
Shift
Sequencing
Press START button to command the Drive to the Enable and
Run state
Press STOP button commands to stop the Drive from the
Run state
Press to display the current reference value and to increase
the reference value and accelerate the drive.
Press to decrease the reference value and decelerate the drive.
Press SHIFT and [-] to change the motor shaft rotation
Display
Motor pot oper.
+0 [rpm] POS
Motor pot oper.
-0 [rpm] NEG
8.1 Motor Potentiometer function
Note!
(Main commands = DIGITAL)
Enable drive, terminal 12 connected to 24VDC
Start, terminal 13 connected to 24VDC
Resetting the speed reference value using Mot pot
function
Press
[STOP] button to stop the motor
Press
[Left arrow] until to “Basic menu”, then [Down
arrow] to “Functions”. [Enter] to motor pot, then
[Enter] to “enab motor pot”, press [Down arrow] to
motor pot reset, then
[Enter].
The diplay will read “ready” until the reference value
is set to zero.
Set the motor pot to “disable” (Enable motor pot
parameter = Disable) if you will want to use an analog
voltage on terminal 1 for speed reference.
Jog function
Note!
This function is enabled as a default setting (Enable jog
parameter = Enabled). Speed reference value = 100 rpm.
(Main commands = DIGITAL)
Enable drive, terminal 12 connected to to 24 VDC
Start, terminal 13 conected to to 24 VDC
Press
[SHIFT and [+] to run, the speed will be displayed
Press
[-] to select the motor shaft rotation
Press
[jog] to run the other direction
Press
[Left arrow] to exit from jog operation
Changing jog reference
Press
[Down arrow] until “Functions”, [Enter], then [Down
arrow] until “Jog reference”, [Enter], using the [Up arrow]/
[Down arrow] keys to change the value and the [Left
arrow] to move the character position, set the reference
value, then
[Enter].
If there are other changes you might want to make to set
up (see Options), do them now, and complete the following
step to put everything into permanent memory.
Saving all values to Permanent Memory:
Press [Left arrow] back to “Configuration” then [Up
arrow] to “basic menu” and [Enter]. Press [Down
arrow] to “save parameters” and [Enter]. Parameters
are now stored permanently.