American Dryer Corp. ADS-464 Clothes Dryer User Manual


 
70
Release the REVERSE Push-button
Does PLC (Programmable Logic Controller) input L.E.D. #18 go “OFF”?
If the answers to these questions are “YES,” wiring to the PLC is correct.
If any answer to these questions is “NO,” refer to Probable Causes below
Tumbler Forward Switch --- PB1
For quick check of the wiring of PB1 to the PLC (Programmable Logic Controller) perform the following
test with the control voltage “ON” (“GREEN” button).
Press the FORWARD Push-button.
Does PLC (Programmable Logic Controller) input L.E.D. #17 light?
Release the REVERSE Push-button.
Does PLC (Programmable Logic Controller) input L.E.D. #17 go “OFF”?
If the answer to these questions are “YES,” wiring to the PLC (Programmable Logic
Controller) is correct.
If the answer to these questions are “NO,” refer to Probable Causes below
a) PROBABLE CAUSES;
1. FUSE 4 ON MAIN ELECTRICAL PANEL
2. FAULTY SWITCHES
3. WIRING BACK TO PLC (Programmable Logic Controller)
b) POSSIBLE SOLUTIONS;
1. Check fuse blown indicator on fuse 4; replace fuse, if necessary and re-test.
2. Check switches using an OHM meter; replace if necessary, and re-test.
3. Refer to ADS-464 Pendant associated wiring diagrams for detailed assemblyand wiring information.
Check ALL circiuts back to PLC (Programmable Logic Controller).
ADS-464 PENDANT ASSEMBLY DIAGRAM
ADS-464 ANNUNCIATOR, PENDANT, and UPPER RTD’S (Resistive Temperature Device)
WIRING DIAGRAM
EMERGENCY STOP (E-Stop) SWITCH --- PB6
If the “Emergency Stop” switch (pendant) does not respond: