American Dryer Corp. ADS-464 Clothes Dryer User Manual


 
51
4. Front Panel BLUE” Light and “RED” Light “ON”
ADS-464 “ON” button does respond ...
a. PROBABLE CAUSES;
1a) EMERGENCY STOP (E-STOP) BUTTONS 1, 2, and 3.
b. POSSIBLE SOLUTIONS;
1b) Verify that ALL EMERGENCY STOP (E-Stop) buttons are pushed in.
EMERGENCY STOP 1 - main enclosed door
EMERGENCY STOP 2 - pendent control
EMERGENCY STOP 3 - rear control panel (2-door models only)
If ALL EMERGENCY STOP (E-Stop) buttons are “disengaged,” press “ON” located on the
main enclosure door.
If “NO,” go to section 3 on page 47
Does the system “GREEN” “ON” light illuminate?
If not, check the EMERGENCY STOP (E-Stop) and drying system “ON/OFF” circuits.
(Refer to ladder diagram.)
5. Front Panel BLUE” (main panel) light, “RED” (sprinkler power) light, and “GREEN” (control
power) light “ON
The system has one or more of the following symptoms;
OPERATOR INTERFACE TERMINAL - no display or displays “LINE FAULT” message
PROGRAMMABLE LOGIC CONTROLLER (PLC) - no indicator lights “ON”
CONVENIENCE OUTLET - no power
HI-LIMIT CONTROLLERS (HLS1 and HLS2) - no display
a. PROBABLE CAUSES;
1a) Fuse 7 -- PLC (Programmable Logic Controller) power
Fuse 8 -- 24 volt DC power
Fuse 9 -- convenience outlet
Fuse 10 -hi-limit controller power
2a) Malfunctioning PLC (Programmable Logic Controller).