Alliance Laundry Systems 504523R3 Clothes Dryer User Manual


 
26 504523
Main collector duct should be sized according to
specifications shown below.
NOTE: Main collector duct should be equipped with
an auxiliary fan that can maintain the duct airflow at
a minimum of 366 m (1200 feet) per minute. If you do
not have a fan, clean the main collector duct at least
twice a year.
D039IE3D
WEATHER HOOD
OR SWEEP ELBOW
(No cap or screen)
WALL
PARAPET
ROOF
180˚ SWEEP
ELBOW
(No cap
or screen)
60.96 cm
(24") MIN.
VERTICAL DUCTHORIZONTAL DUCT
MAIN COLLECTOR DUCT
MAIN COLLECTOR DUCT
Number of Dryers
Minimum Diameter of
Horizontal Collector Duct
Minimum Diameter of
Vertical Collector Duct
2 17.8 cm (7 inches) 20.3 cm (8 inches)
3 20.3 cm (8 inches) 22.9 cm (9 inches)
4 22.9 cm (9 inches) 25.4 cm (10 inches)
5 25.4 cm (10 inches) 27.9 cm (11 inches)
6 27.9 cm (11 inches) 30.5 cm (12 inches)
7 30.5 cm (12 inches) 32.6 cm (13 inches)
8 30.5 cm (12 inches) 35.6 cm (14 inches)
9 32.6 cm (13 inches) 38.1 cm (15 inches)
10 35.6 cm (14 inches) 38.1 cm (15 inches)
11 35.6 cm (14 inches) 40.6 cm (16 inches)