Table PD-36 — Auxiliary Electric Heat Capacity
Total2 Stage1 Stage 2
Unit KW MBH No. of KW MBH KW MBH
Tons Model No. Input
1
Output
1
Stages Input
1
Output
1
Input
1
Output
1
18.00 61.47 1 18.00 61.47 — —
TC*150D3,D4,DW,DK 27.00
4
92.15 2 9.00 30.72 18.00 61.43
12½-15 TC*180B3,B4,BW,BK 36.00 122.94 2 18.00 61.47 18.00 61.47
TC*151 or 181C3,C4,CW 54.00 184.41 2 36.00 122.94 18.00 61.47
TC*210C3,C4,CW,CK 36.00 122.94 2 18.00 61.47 18.00 61.47
17½, 20, 25 TC*240, 300B3,B4,BW,BK 54.00 184.41 2 36.00 122.94 18.00 61.47
TC*211, 241, 301C3,C4,CW 72.00
3
245.88 2 36.00 122.94 36.00 122.94
Notes:
1. Does not include indoor fan power or heat.
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP = x rated cap.
3. Not available on TC*210C.
4. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.
(12½-25 Ton)
Performance
Data
Table PD-37 — Electric Heater Voltage
Correction Factors (Applicable to Auxiliary
Heat Capacity)
Nominal Distribution Capacity
Voltage Voltage Multiplier
208 0.75
240 230 0.92
240 1.00
440 0.84
480 460 0.94
480 1.00
540 0.81
600 575 0.92
600 1.00
Rated Voltage
( )
Voltage
Table PD-38 — Air Temperature Rise Across Electric Heaters (Degree F)
12½ Ton 15 Ton 17½ Ton 20 Ton 25 Ton
5000 CFM 6000 CFM 7000 CFM 8000 CFM 9000 CFM
Three Phase Three Phase Three Phase Three Phase Three Phase
TC*150 TC*180 TC*210 TC*240 TC*300
KW Stages TC*151 TC*181 TC*211 TC*241 TC*301
9.00 1 —————
17.30 1 —————
18.00 1 11.4 9.5 — — —
27.00 2 — 14.2
2
12.2
21
10.7
2
9.5
2
36.00 2 22.8 19.0 16.3 14.2 12.6
54.00 2 34.1 28.5 24.4 21.3 19.0
72.00
2
2 — — 32.5 28.5 25.3
For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
Temp. Rise across Elect. Htr =
KW x 3413
1.08 x CFM
Notes:
1. Not available on TC*210 model.
2. 27KW heater can be used with TCD181C4, TCD211C4, TCD241C4 andTCD301C4 only. Cannot be used with oversized motor.
2