A SERVICE OF

logo

41
RT-PRC002-EN
Performance
Data
(17½ Ton)
High Efficiency
*Indicates both downflow and horizontal units.
Table PD-27 — Evaporator Fan Performance — 17½ Ton — TC*211C — Standard or TXV Refrigeration System
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor 5 HP Standard Motor &
& Field Supplied Extra Field Supplied Low Static Drive (1)
Low Static Drive (2)
3500* 448 0.66 488 0.78 523 0.91 557 1.05 590 1.20 622 1.35 652 1.50
4550* 457 0.90 490 1.03 524 1.17 557 1.32 590 1.48 621 1.64 649 1.80 676 1.97
5600 452 1.14 487 1.30 518 1.45 547 1.60 575 1.75 602 1.91 629 2.08 656 2.26 683 2.43 710 2.63
6300 499 1.63 532 1.76 561 1.94 588 2.10 614 2.26 639 2.43 663 2.60 687 2.79 711 2.99 735 3.19
7000 546 2.11 578 2.31 606 2.52 631 2.71 655 2.89 678 3.07 701 3.25 723 3.44 744 3.64 766 3.85
7700 594 2.75 625 2.98 651 3.21 675 3.43 698 3.64 720 3.84 741 4.03 761 4.23 782 4.44 801 4.65
8400 642 3.52 671 3.78 697 4.03 720 4.27 741 4.51 762 4.73 782 4.95 802 5.16 821 5.38 840 5.60
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-32.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
*Unit applications below 5600 CFM
Electric heaters restricted on applications below 5600 CFM.
Dehumidification (Hot Gas Reheat) or TXV with Frostat and Crankcase Heaters
are required on applications below 5600 CFM.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Note:
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be necessary.
Factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or
premature motor failure. Our product’s warranty will not be
affected.
Table PD-27— Evaporator Fan Performance — 17½ Ton — TC*211C — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive 5 HP Standard Motor & High
Static Drive Accessory
3500* 680 1.65 707 1.80 732 1.95 756 2.11 779 2.27 801 2.43 822 2.60 843 2.77 863 2.94 882 3.11
4550* 703 2.15 729 2.34 754 2.54 779 2.73 803 2.92 827 3.11 849 3.31 871 3.50 892 3.70 913 3.89
5600 736 2.83 761 3.03 785 3.23 807 3.43 829 3.64 851 3.86 872 4.09 893 4.32 914 4.56 935 4.80
6300 759 3.38 783 3.59 807 3.82 830 4.04 853 4.27 874 4.49 894 4.72 913 4.95 933 5.19 952 5.43
7000 788 4.07 810 4.29 831 4.51 852 4.74 874 4.97 895 5.22 917 5.47 937 5.72 957 5.97 975 6.22
7700 821 4.87 841 5.10 861 5.34 881 5.59 900 5.83 919 6.07 939 6.32 958 6.58 978 6.85 997 7.12
8400 858 5.82 876 6.06 894 6.30 912 6.55 930 6.81 949 7.08 967 7.34 984 7.60 1002 7.87
7.5 Oversize Motor & Drive
5 HP Standard Motor &
High Static Drive Accessory