Table PD-17 — Evaporator Fan Performance — 12½ Ton — TC*150D — Continued
External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Sheaves 3 HP Standard Motor & High Static Drive Accessory
4000 786 1.70 813 1.81 841 1.91 867 2.02 893 2.12 919 2.22 943 2.32 966 2.41 989 2.50 1011 2.60
4500 806 2.06 834 2.19 861 2.31 886 2.43 911 2.56 935 2.67 960 2.79 983 2.90 1005 3.02 1028 3.13
5000 830 2.48 856 2.62 882 2.76 907 2.89 931 3.02 955 3.16 977 3.30 1001 3.44 1022 3.56 1045 3.70
5500 861 2.93 884 3.10 906 3.25 930 3.41 953 3.56 976 3.70 999 3.86 1021 4.00 1043 4.15 1064 4.31
6000 894 3.43 916 3.61 938 3.79 959 3.97 980 4.15 1000 4.31 1019 4.46 1040 4.62 1061 4.78 1082 4.95
5 HP Oversize Motor & Sheaves
(12½ Ton)
Standard Efficiency
Performance
Data
Factory supplied motors, in commercial equipment, are definite
purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the
full horsepower range of our fan motors as shown in our
tabular data will not result in nuisance tripping or premature
motor failure. Our product’s warranty will not be affected.
5 HP Oversize Motor & Field Supplied Drive
For Standard Evaporator Fan Speed (RPM), reference Table PD-31.
For Oversized Evaporator Fan Speed (RPM), reference Table PD-33.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters.
No accessories or options are included in pressure drop data.
Refer to Table PD-35 to determine add’l static pressure drop due to other options/accessories.
Notes:
1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary.
2. 5 HP Oversized Motor with Field Supplied Motor Sheave IVL40 Required. Field Supplied Belt
may be necessary.
3. For 380V/60 Hz units, the oversized motor is used as the standard motor. Refer to “Motor &
Sheave/Fan Speed” tables to determine operating range.
Table PD-17 — Evaporator Fan Performance — 12½Ton — TC*150D
External Static Pressure (Inches of Water)
.10 .20 .30 .40 .50 .60 .70 .80 .90 1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field 3 HP Standard Motor & Sheaves
Supplied Low Static Drive
4000 565 0.93 599 1.03 632 1.15 663 1.27 695 1.38 727 1.48 757 1.59
4500 571 1.10 603 1.21 634 1.31 665 1.43 694 1.56 723 1.69 750 1.82 778 1.94
5000 547 1.18 581 1.30 613 1.42 643 1.54 672 1.67 700 1.78 727 1.91 755 2.05 781 2.19 806 2.34
5500 595 1.55 627 1.68 656 1.81 685 1.94 711 2.08 737 2.21 763 2.34 788 2.47 813 2.62 837 2.77
6000 643 1.99 673 2.12 701 2.26 727 2.41 752 2.56 777 2.71 801 2.85 825 2.99 848 3.13 871 3.27