American Dryer Corp. ML-55HS Clothes Dryer User Manual


 
15
NOTE: When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible
materials, the opening must be 2-inches (5.08 cm) larger than the duct (ALL the way around).
The duct must be centered within this opening.
a. Outside Ductwork Protection
1) To protect the outside end of horizontal ductwork from the weather, a 90° elbow bent downward
should be installed where the exhaust exits the building. If the ductwork travels vertically up
through the roof, it should be protected from the weather by using a 180° turn to point the opening
downward. In either case, allow at least twice the diameter of the duct between the duct opening
and the nearest obstruction.
IMPORTANT: DO NOT use screens, louvers, or caps on the outside opening of the exhaust
ductwork.
2. Single Dryer Venting
Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct should
be laid out in such a way that the ductwork travels as directly as possible to the outdoors with as few turns
as possible. It is suggested that the use of 90° turns in the ducting be avoided; use 30° and/or 45° angles
instead. The shape of the exhaust ductwork is not critical so long as the minimum cross section area is
provided.
IMPORTANT: Minimum duct size for a dryer that is vented horizontally is 8-inches (20.32 cm) for a
round duct or an equivalent of 54 square inches (348.4 square centimeters). THE
DUCT SIZE MUST NOT BE REDUCED ANYWHERE DOWNSTREAM
OF THE DRYER.
IMPORTANT: Exhaust back pressure measured by a manometer at each basket (tumbler) exhaust
duct area must not exceed 0.3 inches (0.74 mb) of water column (W.C.).
IMPORTANT: Minimum duct size for a dryer that is vented vertically is 8-inches (20.32 cm) for a
round duct or an equivalent of 54 square inches (348.4 square centimeters). THE
DUCT SIZE MUST NOT BE REDUCED ANYWHERE DOWNSTREAM
OF THE DRYER.